Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM00321
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/07/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/06/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 05/05/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. ALL MC TO BE SECURED WITHIN 12" OF TERMINATIONS NEC 330.30 2. PROPERLY IDENTIFY CURRENT CARRYING CONDUCTORS NEC 200 AND 310 3. BOX EXTENDERS NEEDED IN MILL WORK - NEC 314.20 4. ALL ROOFTOP EQUIPMENT TO BE SECURELY MOUNTED NEC 110.13 5. PROPERLY IDENTIFY ALL EQUIPMENT WITH PERMANENT LABELS - NEC 110 6. STRANDED NOT TO BE UNDER GROUND SCREW - NEC 110 7. ROOF TOP SERVICE RECEPTACLE NOT WORKING - NEC 210 TRANSFORMER 1. NEED 8" SIDE CLEARANCE - NEC 110 2. MISSING BREAKER BLANK - NEC 110 3. PROPERLY IDENTIFY ALL EQUIPMENT - NEC 110 4. OVER CURRENT ON SECONDARY TO HIGH - NEC 110 5. GROUNDING ELECTRODE CONDUCTOR TO GO TO WATER #4 OR STEEL #2 - NEC 250.30 AND NEEDS PHYSICAL PROTECTION - NEC 250.30 A5 |