Permit: T08CM00321

Parcel: 10408095C

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/07/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/06/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
05/05/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. ALL MC TO BE SECURED WITHIN 12" OF TERMINATIONS
NEC 330.30
2. PROPERLY IDENTIFY CURRENT CARRYING CONDUCTORS
NEC 200 AND 310
3. BOX EXTENDERS NEEDED IN MILL WORK - NEC 314.20
4. ALL ROOFTOP EQUIPMENT TO BE SECURELY MOUNTED
NEC 110.13
5. PROPERLY IDENTIFY ALL EQUIPMENT WITH PERMANENT LABELS - NEC 110
6. STRANDED NOT TO BE UNDER GROUND SCREW - NEC 110
7. ROOF TOP SERVICE RECEPTACLE NOT WORKING - NEC 210

TRANSFORMER
1. NEED 8" SIDE CLEARANCE - NEC 110
2. MISSING BREAKER BLANK - NEC 110
3. PROPERLY IDENTIFY ALL EQUIPMENT - NEC 110
4. OVER CURRENT ON SECONDARY TO HIGH - NEC 110
5. GROUNDING ELECTRODE CONDUCTOR TO GO TO
WATER #4 OR STEEL #2 - NEC 250.30 AND NEEDS PHYSICAL PROTECTION - NEC 250.30 A5