Inspection History: MECHANICAL - PROGRESS

Date Description Inspector Results Comments
06/19/2008 MECHANICAL - PROGRESS Approved IVRS - Inspection :*
- FLUE PIPE ON REZNOR FURNACE IN WRONG
DIRECTION OF FLOW
- REMOVE GAS PIPE SUPPORT FROM UNIT
- SEAL DUCT AND PROVIDE DAMPER IN TECH. ROOM

OK FOR TILES
06/13/2008 MECHANICAL - PROGRESS Partial Approval IVRS - Inspection :*
1. INSTALL FLEX DUCT PER DETAIL (2/M3.1)
2. PROVIDE TIE WIRES TO STRUCTURE ON REGISTERS
OVER 25 POUNDS LESS THAN 25 POUNDS CAN TIE TO
GRID SYSTEM
3. SEAL EXHAUST DUCT ABOVE GRID
4. INSULATE RETURN CANS ABOVE GRID
5. PROVIDE CORRECT DIFFUSERS IN RESTROOMS
6. SEAL AROUND DUCTS PENETRATING WALLS PER PLANS
7. REMOVE FOIL TAPE FROM FLUE PIPE
8. PROVIDE DAMPERS IN EXHAUST DUCT PER PLANS