Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/27/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 02/26/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* #236 ONLY - CHECK OTHERS 1. #10 & #12 EQUIPMENT GROUND NOT TO BE UNDER SAME TERMINATION ON GROUND BAR - NEC 110.3B 2. 2 NEUTRALS NOT ALLOWED UNDER SAME SCREW ON NEUTRAL BAR - NEC 408 3. COVER PLATE MISSING 4. NAILPLATE NEEDED WHERE HOLE IS 1 1/4 OR LESS FROM STUD FACE 5. DO NOT COVER WALLS BEFORE INSPECTION |