Permit: T08CM00300

Parcel: 114461260

Inspection Status: Not ready for Inspection

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
02/28/2008 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
02/26/2008 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
STILL NEED TO FINISH PLUMBING NOTES FROM PREVIOUS INSPECTION. PROVIDE THE DEVICE TO LEAVE FIREPLACE DAMPER OPEN MIN. 1"
LEFT GAS CARD
02/20/2008 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
PRESSURE TEST OK
INSTALL A LOG LIGHTER VALVE OUTSIDE OF FIREPLACE
NOT A QUARTER TURN GAS LOCK. FIREPLACE IS DESIGNED FOR WOOD. LOG LIGHTER VALVE MAY BE USED WITH A DECORATIVE APPLIANCE

SECURE STRUT TO WALL. WILL NEED TO SECURE PIPING AT VALVE TO NEW FURNACE AT TIME OF INSTALLATION
RECALL FOR INSPECTION TO OBTAIN GAS CLEARANCE AFTER INSTALLING APPLIANCE
02/11/2008 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
- REMOVE TEE FOR BARBEQUE LOCATED BELOW WOOD
OVER HANG.
- RETEST
- REMOVE SHARP EDGES FROM STRUT ON ROOF. 1 1/2" MIN. CLEARANCE ABV ROOF REQUIRED.
- PLAN REQUIRED FOR NEW INSTALLATION OF GAS SYSTEM
- HAVE APPROVED VALVES ON SITE
02/01/2008 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
- PROVIDE A CITY APPROVED PLAN SHOWING NEW GAS SYSTEM.
- INCLUDE LOCATION OF BARBEQUE AND OVERHEAD PORCH AS WELL AS BTU DEMANDS AND DISTANCE
- PROVIDE PIPE CLAMPS ON PIPING.
- DO NOT USE CONDUIT CLAMPS
- PIPING MAY NOT TOUCH ROOF - PROVIDE SUPPORTS IN ALL AREAS
- PROVIDE AGA VALVES
- INSTALL FURNACE AND HAVE IT INSPECTED