Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMP POWER FOR TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/21/2008 | ELECTRIC - TEMP POWER FOR TEST | Approved | IVRS - Inspection :* 1) SUBJECT TO BOND POSTING |
|