Permit: T08CM00281

Parcel: 13705507B

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
06/18/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
06/13/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. MC CABLE TO BE SUPPORTED WITHIN 12" OF TERMINATE AND AT 6' INTERVALS PER NEC
2. WHEN USING SEISMIC WIRES TO SUPPORT CABLE OR RACEWAYS IT MUST BE TIED OFF AT BOTH ENDS
PER NEC 300 AND 330.30
06/12/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
04/25/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK RESTROOMS
04/23/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS EXCEPT RESTROOM WALLS
04/22/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. STRAP MC WITHIN 12" OF TERMINATIONS
2. PROVIDE NAIL PLATES AS NEEDED
04/17/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK UNDERGROUND FOR CASH WRAP