Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/18/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 06/13/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. MC CABLE TO BE SUPPORTED WITHIN 12" OF TERMINATE AND AT 6' INTERVALS PER NEC 2. WHEN USING SEISMIC WIRES TO SUPPORT CABLE OR RACEWAYS IT MUST BE TIED OFF AT BOTH ENDS PER NEC 300 AND 330.30 |
|
| 06/12/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 04/25/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK RESTROOMS |
|
| 04/23/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS EXCEPT RESTROOM WALLS |
|
| 04/22/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. STRAP MC WITHIN 12" OF TERMINATIONS 2. PROVIDE NAIL PLATES AS NEEDED |
|
| 04/17/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK UNDERGROUND FOR CASH WRAP |