Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/28/2010 | FRAMING | Approved | IVRS - Inspection :* | |
| 02/04/2010 | FRAMING | Partial Approval | IVRS - Inspection :* 1) STRAP H.D.'S-OK TO COVER |
|
| 11/02/2009 | FRAMING | Partial Approval | IVRS - Inspection :* 1) MAIN HOUSE OK |
|
| 10/22/2009 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FIRE STOP AT FURR DOWNS AS INDICATED 2) ELECTRICAL TO SMOKE ALARM, WIRE INTERLOCKING ALARMS SHALL BE IN SAME RACEWAY 3) PORTECT ABS PIPE CLOSER THAT 1 1/2" FROM FACE OF STUDS 4) REVISE PLANS TO REFLECT AS BUILT ON SHEARWALLS 5) HAVE ARCHITECT OF RECORD REVISE DRAWING AND SPECIFY CORRECTIONS AT SHEARWALLS |
|
| 04/24/2009 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) BLOCK ALL REGISTER BOXES 2) NAIL STOP PIPES AND WIRES WITHIN 1 1/2" OF SURFACE 3) GROUND METAL BOXES 4) SECURE WIRES WITHIN 8" OF BOX 5) MAKE UP GROUNDS 6) COMPLETE ALL WIRING |