Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T08CM00278
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/22/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 07/16/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* AH-1 UNIT SHUTDOWN NO AUDIBLE AH-2 UNIT DID NOT SHUT DOWN AND NO AUDIBLE |
|
| 05/28/2008 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* DUCT SMOKE DETECTOR TEST AHU-1 AHU-2 |
|
| 05/19/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* AHU-1 HANDLE MISSING ON SUPPLY DAMPER BOILER PIPING NOT INSULATED VERIFY DUCT SMOKE DETECTORS ALARM STATUS PRIOR TO TESTING MECHANICAL CONTRACTOR ON SITE FOR SMOKE TESTS |