Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM00278
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/24/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* ALL CORRECTIONS MADE NO PROBLEMS IS REST OF THIS INSPECTION |
|
| 06/23/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CONTRACTOR TO RESCHEDULE |
|
| 05/13/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. GROUND LUG @ CHILLER NOT LISTED FOR TWO CONDUCTORS - NEC 110.3B 2. GUTTER IS UNDERSIZED AT CHILLER - NEC 366.58 3. GROUND GUTTER WITH EQUIPMENT GROUND - 314.40D 4. IDENTIFY CHILLER DISCONNECT - NEC 110.22 5. DISCONNECT OVERFUSED AND AT "P1" - NEC 110.3B 6. GROUND LUGS IN DISCONNECT NOT LISTED FOR TWO CONDUCTORS - NEC 110.3B 7. J-BOX INTO DISCONNECT UNDERSIZED - NEC 314.28 8. GROUND ENCLOSURES WITH EQUIPMENT GROUND - 314.40D 9. PROPERLY IDENTIFY ALL EQUIPMENT/DISCONNECTS AS TO WHAT THEY SERVE - NOT BY CKT. # -- NEC 110.22 10. SHEETMETAL SCREWS NOT ALLOWED FOR GROUND CONNECTION -- NEC 250.8 11. REMOVE ALL PAINT UNDERGROUND LUGS - NEC 250.12 12. BOND AROUND REDUCING WASHERS - NEC 250.4 DUE TO TIME LIMITATIONS THIS IS A PARTIAL INSPECTION ONLY |