Permit: T08CM00278

Parcel: 12501001A


Addresses:

2700 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08CM00278

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/24/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
ALL CORRECTIONS MADE
NO PROBLEMS IS REST OF THIS INSPECTION
06/23/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CONTRACTOR TO RESCHEDULE
05/13/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. GROUND LUG @ CHILLER NOT LISTED FOR TWO CONDUCTORS - NEC 110.3B
2. GUTTER IS UNDERSIZED AT CHILLER - NEC 366.58
3. GROUND GUTTER WITH EQUIPMENT GROUND - 314.40D
4. IDENTIFY CHILLER DISCONNECT - NEC 110.22
5. DISCONNECT OVERFUSED AND AT "P1" - NEC 110.3B
6. GROUND LUGS IN DISCONNECT NOT LISTED FOR TWO CONDUCTORS - NEC 110.3B
7. J-BOX INTO DISCONNECT UNDERSIZED - NEC 314.28
8. GROUND ENCLOSURES WITH EQUIPMENT GROUND - 314.40D
9. PROPERLY IDENTIFY ALL EQUIPMENT/DISCONNECTS AS TO WHAT THEY SERVE - NOT BY CKT. # -- NEC 110.22
10. SHEETMETAL SCREWS NOT ALLOWED FOR GROUND CONNECTION -- NEC 250.8
11. REMOVE ALL PAINT UNDERGROUND LUGS - NEC 250.12
12. BOND AROUND REDUCING WASHERS - NEC 250.4

DUE TO TIME LIMITATIONS THIS IS A
PARTIAL INSPECTION ONLY