Permit: T08CM00276

Parcel: 13331159W


Addresses:

8838 E BROADWAY BL

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
06/30/2008 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
1. OK FOR CEILING TILES
2. WATER HEATER VENT OFFSET NOT TO EXCEED 60 DEG.
3. PROVIDE 1" CLEARANCE TO COMBUSTIBLES
4. PROVIDE FULL LENGTH HANGER RODS ON HOOD
NO SPLICES
5. DO NOT USE PLUMBERS TAPE TO SUPPORT
WATER HEATER VENT
06/24/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
PROVIDE SADDLES ON FLEX DUCT