Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/20/2009 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 11/18/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) PROVIDE ENGINEERS APPROVAL TO EXCEED 8' FLEX LENGTH ALLOWED 2) OK TO TILE 1ST FLOOR |
|
| 11/13/2009 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 11/04/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) DUCT FIRE/SMOKE DETECTOR DAMPER INSTALLATION X 5 OK 2) PROVIDE MEANS FO ACTIVATION |
|
| 10/27/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 10/21/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 10/19/2009 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 10/08/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) WEST SIDE 1ST FLOOR CORRIDOR OK TO ROCK-MECH ONLY 2) CORRIDOR SOFFIT NORTH OF RESTROOMS 1ST FLOOR OK TO ROCK-MECH ONLY |
|
| 10/05/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) ALL PVC JOINTS TO HAVE PRIMER, ALL PRIMER TO BE PURPLE IN COLOR 2) HORIZONTAL UNIT IN LAUNDRY DOES NOT HAVE PROPER CLEARANCE 3) ALL HORIZONTAL UNITS TO HAVE PROPER CLEARANCE 4) CEILING CANS TO BE FRAMED MIN. 3 SIDES 5) PROVIDE O.S.A. DAMPERS |
|
| 09/24/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK TO ROCK RESTROOMS ALL 1ST FLOOR |
|
| 09/18/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) FRAME THE REST OF RESTROOM CEILINGS, INSTALL FANS, THEN RESCHEDULE INSPECTION 2) OK TO SHEETROCK 10 UNITS AT NORTH END OF BLDG ONLY, 1ST FLOOR |
|
| 09/17/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) PROVIDE SCREWS AT ALUM. PIPE TO RIDGID DUCT CONNECTIONS 2) ROOM 136 NO E.F. OR DUCT INSTALLED |
|
| 09/11/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) V TAC DUCT OK TO COVER |
|
| 09/04/2009 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 09/03/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. PROVIDE PROPER CLEARANCE AND ACCESS TO ALL EQUIPMENT 2. PROVIDE FIRE CAULK AROUND EXHAUST FAN DUCT AT CEILING PENETRATIONS THIRD FLOOR RESTROOM EXHAUST FANS OK TO COVER |
|
| 04/02/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* AHU SUPPORTS 1ST FLOOR OK |