Permit: T08CM00263

Parcel: 11616301J


Addresses:

705 N FREEWAY

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
02/24/2009 PLUMBING - ROUGH, SOIL Approved OK TO POUR MIDDLE SECTION
01/14/2009 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
UPPER LEVEL, BELOW SLAB SOIL PIPE BETWEEN COLS. K-T WITH TEST OK
01/12/2009 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
FIRST FLOOR ROUGH IN CORRECTIONS MADE OK
OK TO COVER
WATER TEST, ONE RISER TO TEN FEET OK
01/08/2009 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1. VERTICAL X HORIZONTAL CHANGE OF DIRECTION TO BE A SWEEP
2. REQUIRE 2X THE PIPE DIAMETER BETWEEN TRAP WEIR AND POINT OF VENT
3. HORIZONTAL VENTING BELOW FLOOD RIM DUE TO STRUCTURAL CONDITIONS
4. OK TO COVER UNAFFECTED AREAS
5. RETEST AFTER CORRECTIONS MADE
6. TRAP SEAL DEPTH TO BE 2"-4" MAX.
01/07/2009 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
YOU MAY NOT TEST PVC WITH AIR
TEST PER PLAN SPECS, SEE PAGE MP1
01/02/2009 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
1) PLAN SEEMS TO BE MISSING ESSENTIAL INFORMATION IE. DWV MATERIAL TYPES, WATER SUPPLY, INSULATION, GAS, ETC... MATERIAL TYPES
2) CONTINUED NOT READYS MAY RESULT IN A REINSPECTION FEE