Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/30/2008 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* | |
| 06/16/2008 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 1. ALL FITTINGS, INCLUDING TEST FITTINGS, ARE TO BE INSTALLED PER THEIR LISTING A BLAKE TEE IS LISTED AS A VERTICAL, SURFACE WALL CLEANOUT USE DIRECTIONAL FITTINGS FOR TEST 2. IT APPEARS THAT THE GREASE WASTE FOR THIS UNIT ALSO SERVES AT LEAST TWO OTHER UNITS. EACH UNIT IS TO HAVE ITS OWN INTERCEPTOR ALSO, IT LOOKS LIKE THE INTERCEPTOR WAS RELOCATED WITHOUT PERMITS OR INSPECTIONS AS THE CLEANOUTS ARE CURRENTLY ACTING AS AREA DRAINS 3. REMEMBER ALL CHANGES TO THE PLAN ARE TO BE ACCOMPANIED BY REDLINE DRAWINGS AT THE TIME OF THE INSPECTION 4. PLEASE PROVIDE HEALTH DEPT. PLAN 5. OK TO COVER UNDERGROUND 03005 WILL BE APPROVED AFTER TYPE "K" VERIFICATION |