Inspection History: ELECTRIC - FINAL

Permit Number - T08CM00231

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/30/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/29/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
FINISH ITEM #7 & 8 LAST INSP.
07/28/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. SUPPORT BOXES UNDER COUNTER
2. MAINTAIN WORKING CLEARANCES AT DISCONNECT
3. ALL KITCHEN RECEPTACLES TO BE GFCI PROTECTED - 210.8
4. WHERE IS WATER HEATER GROUND?
5. SEAL RACEWAYS ENTERING WALK-IN PER 300.7
6. LABEL CIRCUIT DIRECTORIES AS PER 408.4 - NO ABBREVIATIONS
7. FRONT EXIT LIGHT NOT WORKING
8. SUPPORT VDV CABLING 725.24, 800.24, 300.11

ROOF:
1. LABEL DISCONNECTING MEANS
2. NEED MAINTENANCE RECEPTACLE 210.63
3. TIGHTEN LOOSE FITTINGS
4. PROPERLY SEAT BOND SCREW
5. SUPPORT SATELLITE CABLE UP OFF ROOF 820