Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM00231
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/30/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
07/29/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* FINISH ITEM #7 & 8 LAST INSP. |
|
07/28/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SUPPORT BOXES UNDER COUNTER 2. MAINTAIN WORKING CLEARANCES AT DISCONNECT 3. ALL KITCHEN RECEPTACLES TO BE GFCI PROTECTED - 210.8 4. WHERE IS WATER HEATER GROUND? 5. SEAL RACEWAYS ENTERING WALK-IN PER 300.7 6. LABEL CIRCUIT DIRECTORIES AS PER 408.4 - NO ABBREVIATIONS 7. FRONT EXIT LIGHT NOT WORKING 8. SUPPORT VDV CABLING 725.24, 800.24, 300.11 ROOF: 1. LABEL DISCONNECTING MEANS 2. NEED MAINTENANCE RECEPTACLE 210.63 3. TIGHTEN LOOSE FITTINGS 4. PROPERLY SEAT BOND SCREW 5. SUPPORT SATELLITE CABLE UP OFF ROOF 820 |