Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/04/2009 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 02/18/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* RECEIVED LETTER OF TORQUE & GFI MAIN BRKR TEST |
|
| 02/17/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 02/11/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. PROVIDE LETTER OF TORQUE FOR SES EQUIP. 2. INSTALL BUSHED ENDS WHERE CONDUIT EMERGES PER 300 NEC 3. PROVIDE GFI MAIN TEST PRIOR TO ENERGIZE PER MANUF. 230.95 4. LASH SECONDARY CONDUCTORS AS PER MANUF. |
|
| 12/17/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK SOFFITS AT ENTRIES |
|
| 12/15/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK POLE BASE ON WEST PARKING |
|
| 06/27/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. NEED TO HAVE 02010 UNDERGROUND ELECTRIC ADDED TO PERMIT 2. OK U.G 5 - 2" FOR TELEPHONE & 10 - 2 1/2 FOR FUTURE PANELS FROM SEC LOCATION TO EDGE OF POUR STRIP ALONG SOUTHSIDE OF BUILDING |