Permit: T08CM00224

Parcel: 14026045A

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T08CM00224

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
03/04/2009 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
02/18/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
RECEIVED LETTER OF TORQUE & GFI MAIN BRKR TEST
02/17/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
02/11/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. PROVIDE LETTER OF TORQUE FOR SES EQUIP.
2. INSTALL BUSHED ENDS WHERE CONDUIT EMERGES
PER 300 NEC
3. PROVIDE GFI MAIN TEST PRIOR TO ENERGIZE
PER MANUF. 230.95
4. LASH SECONDARY CONDUCTORS AS PER MANUF.
12/17/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK SOFFITS AT ENTRIES
12/15/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK POLE BASE ON WEST PARKING
06/27/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. NEED TO HAVE 02010 UNDERGROUND ELECTRIC ADDED TO PERMIT
2. OK U.G 5 - 2" FOR TELEPHONE & 10 - 2 1/2 FOR FUTURE PANELS FROM SEC LOCATION TO EDGE OF POUR STRIP ALONG SOUTHSIDE OF BUILDING