Permit: T08CM00223

Parcel: 14026045A

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T08CM00223

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
03/04/2009 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
02/18/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
RECEIVED LETTER OF TORQUE & GFI MAIN BRKR TEST
02/17/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
02/11/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. PROVIDE LETTER OF TORQUE FOR SES EQUIP.
2. INSTALL BUSHED ENDS ON CONDUITS
3. PROVIDE GFI MAIN TEST PER MANUF. COPY
TO INSPECTOR 230.95
4. LASH SECONDARY CONDUCTORS AS PER MANUF.
12/03/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK U.G CONDUIT FOR POLE LTG.
2. OK WAREHOUSE LTG. INTERIOR ROUGH
3. SES NOT INSPECTED YET
11/05/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK EAST & WEST SOFFIT LTG
2. OK CONDUITS FOR SUMPS AT LOADING DOCKS
11/03/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK ENTRY SOFFITS AND WALLS AT ENTRIES
EXCEPT WEST ENTRY
10/30/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
There is no access to the site.| 920*
NO ONE ON SITE FOR INSPECTION 4:20 PM
10/08/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK HOUSE PANEL, X-FORMER FEEDERS AND WATER, SPRINKLER, X-FORMER AND GEAR GROUNDING
UNDER SLAB AT EAST END OF BLD.
06/27/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CALLED IN ERROR
06/19/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK PHONE & POWER FEEDERS BELOW SLAB BLD. #4