Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T08CM00208
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/27/2008 | FRAMING | Approved | IVRS - Inspection :* | |
03/25/2008 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) LOOSE AB'S GARAGE EAST WALL 2) LOOSE AB'S GARAGE SHEARWALL 3 3) LOOSE AB'S SHEARWALL 4 MASTER BATH 4) COMPLY WITH SHEAR TRANSFER DETAIL 5/D3 16D NAILS 4" ON CENTER TRUSS TO 2 X 12 5) MISSING HTC4 CLIPS INTERIOR SHEAR TRANSFER 6) MASTER BEDROOM PER DETAIL 3/D5 7) DAMAGED FIREBLOCK MASTER BATH WEST WALL 8) CHECK RED HEADS THRU-OUT |