Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/09/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/05/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* LISTING TO BE BY A "NRTL" FOR FLOW CABINET NOT SELF CERTIFICATION OR EUROPEAN |
|
| 05/22/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) NEED CIRCUIT DIRECTORY-OLD PANEL (408.4) PROVIDE MFG INSTRUCTIONS 2) RECEPTACLE COVER TO BE WEATHER PROOF WETHER OR NOT PLUGED INTO 406.8 3) PLEASE VERIFY LISTING FLOW CABINET 4) PANEL DIRECTORY TO BE PER 408.4 5) INSTA HOT BREAKERS TO BE 40 AMP |