Permit: T08CM00189

Parcel: 12810082A


Addresses:

5330 E BROADWAY BL

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
07/08/2008 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
1. PROVIDE A SECONDARY DRAIN PAN UNDER FAN COIL
2. SUPPORT DRAIN LINE FROM CONDENSATE PUMP
3. SECONDARY DRAIN TO BE TERMINATED TO A CONSPICUOUS LOCATION.
4. OK FOR CEILING TILES
5. LEAVE OUT AROUND FAN COIL
06/30/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK TO SHEETROCK HARD LIDS
EXTERIOR INSULATION NOT NECESSARY IF LINEAR DIFFUSERS ARE LINED. SUPPORT CEILING DIFFUSERS.
06/25/2008 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
06/24/2008 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. ALL SUPPLY AND RETURN DUCT TO BE INSULATED PER PLANS AND SPECS MIN. R-5
2. ALL LINEAR DIFFUSER BOXES TO BE INSULATED PER PLANS AND SPECS
3. SHOW REVISION ON CONDENSATE DRAIN
05/27/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
SUSPENDED ROUGH DUCT OK TO INSULATE