Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T08CM00189
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/08/2008 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* 1. PROVIDE A SECONDARY DRAIN PAN UNDER FAN COIL 2. SUPPORT DRAIN LINE FROM CONDENSATE PUMP 3. SECONDARY DRAIN TO BE TERMINATED TO A CONSPICUOUS LOCATION. 4. OK FOR CEILING TILES 5. LEAVE OUT AROUND FAN COIL |
|
06/30/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK TO SHEETROCK HARD LIDS EXTERIOR INSULATION NOT NECESSARY IF LINEAR DIFFUSERS ARE LINED. SUPPORT CEILING DIFFUSERS. |
|
06/25/2008 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
06/24/2008 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. ALL SUPPLY AND RETURN DUCT TO BE INSULATED PER PLANS AND SPECS MIN. R-5 2. ALL LINEAR DIFFUSER BOXES TO BE INSULATED PER PLANS AND SPECS 3. SHOW REVISION ON CONDENSATE DRAIN |
|
05/27/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* SUSPENDED ROUGH DUCT OK TO INSULATE |