Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM00189
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/25/2008 | ELECTRIC - FINAL | Approved | ||
07/23/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. EM LIGHTS NOT WORKING 2. RECEPT WITH OPEN NEUTRAL. NO POWER. 3. USE ALL HARDWARE TO MOUNT RECEPT IN INDUSTRIAL COVERS. 4. FINISH WORK 5. RECEPT TO BE MOUNTED SECURELY TO WALLS AND FLUSH WITH PLATES 6. INSTALL BOND SCREW FOR DISCONNECTS 7. NEED GFI SERVICE RECEPT WITHIN 25' OF AC UNITS 8. ROOFTOP UNITS OVER FUSED 9. SWITCH FOR EXHAUST FAN NOT WORKING 10. INSTALL WEATHERHEAD FOR WIRES TO SAT. DISH 11. GROUND SAT DISH 12. REMOVE OLD WIRING AND RACEWAYS FROM ROOF 13. OUTSIDE LIGHTS NOT WORKING 14. CHECK ALL WORK COMPLETE THEN RECALL 15. NEED HANDLE TIE OR CIRCUITS TO OFFICE FURNITURE |