Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM00188
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/03/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
10/29/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. RECEPTACLES IN REPAIR AREA TO BE GFI PROTECTED 2. RECEPTACLES IN REPAIR AREA TO BE ABOVE 18" THIS IS HAZARDOUS LOCATION 3. LOCATION OF EM LIGHTS NOT PER PLAN 4. BREAKERS IN PANEL TO BE RATED 22KAIC CHART PROVIDED IS FOR 100 AMP TYPE PLAN CALLS FOR 22KAIC RATING |