Permit: T08CM00188

Parcel: 13602002Q


Addresses:

8178 E 22ND ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08CM00188

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/03/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/29/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. RECEPTACLES IN REPAIR AREA TO BE GFI PROTECTED
2. RECEPTACLES IN REPAIR AREA TO BE ABOVE 18" THIS IS HAZARDOUS LOCATION
3. LOCATION OF EM LIGHTS NOT PER PLAN
4. BREAKERS IN PANEL TO BE RATED 22KAIC
CHART PROVIDED IS FOR 100 AMP TYPE
PLAN CALLS FOR 22KAIC RATING