Permit: T08CM00186

Parcel: 13609014B


Addresses:

10355 E 29TH ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08CM00186

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/19/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/16/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
FINISH PREVIOUS ITEMS AND INSTALL AS PER PLANS
06/12/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
COMPLETE ALL ITEMS FROM PREVIOUS INSPECTION
HAVE 100% COMPLETE FOR NEXT INSPECTION
TO AVOID REFEE. ELECTRICIAN TO GO THROUGH ENTIRE JOB AND INSTALL PER PLANS & NEC
06/09/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL PROTECTIVE BUSHING ON CONNECTORS WITH CONDUCTORS LARGER THAN #4
2. USE PROPER COLOR CODING OF WIRES 277/480V
3. HAVE CUT STRANDS ON GROUNDING ELECTRODE CONDUCTOR
4. INSTALL NEUTRAL KIT HN623 IN SERVICE DISCONNECT
5. INSTALL MAIN BONDING JUMPER SERVICE DISCONNECT
6. GROUNDING ELECTRODE CONDUCTOR TO TERMINATE ON NEUTRAL BAR IN DISCONNECT AND XFMR
7. BOND METER ENCLOSURES
8. MARK "SERVICE DISCONNECT"
9. INSTALL PLACARD FOR SERIES RATING
SEE NOTE 4 SHEET E2
10. TO INSTALL CLASS J FUSES ONLY
11. INSTALL NEUTRAL AT PANEL "A" SO COVER CAN BE INSTALLED
12. NEED PANEL DIRECTORIES. LABEL PANELS
13. TIGHTEN ALL FITTINGS
14. FINISH WORK. HAVE ELECTRICAL CONTRACTOR GO THROUGH ENTIRE JOB INSTALL PER PLAN & NEC