Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T08CM00185
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/14/2008 | ELECTRIC - ABOVE CEILING | Approved | ||
07/28/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
07/25/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : There is no access to the site.| 920* LOCKED NO ACCESS |
|
07/24/2008 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1. NEED SUPPORT WIRES FOR FIXTURES 2. SUPPORT VDV CABLING 725.24, 800.24, 300.11 3. ATTACH FIXTURES TO GRID 410.16 4. MC TO BE SUPPORTED PER 300.11 5. SUPPORT WIRES FOR ALL FIXTURES |
|
07/22/2008 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1. POST BOND FOR TEMP POWER FOR TEST 2. CONDUCTORS (FEEDERS TO HILL PHOENIX UNIT) SHOULD BE 3/0 CU MIN. PER 310.15 NEC |
|
06/12/2008 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* OK RESTROOM WALLS, HARD LIDS |