Permit: T08CM00185

Parcel: 137055110

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T08CM00185

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
08/14/2008 ELECTRIC - ABOVE CEILING Approved
07/28/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
07/25/2008 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
There is no access to the site.| 920*
LOCKED NO ACCESS
07/24/2008 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1. NEED SUPPORT WIRES FOR FIXTURES
2. SUPPORT VDV CABLING 725.24, 800.24, 300.11
3. ATTACH FIXTURES TO GRID 410.16
4. MC TO BE SUPPORTED PER 300.11
5. SUPPORT WIRES FOR ALL FIXTURES
07/22/2008 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1. POST BOND FOR TEMP POWER FOR TEST
2. CONDUCTORS (FEEDERS TO HILL PHOENIX UNIT)
SHOULD BE 3/0 CU MIN. PER 310.15 NEC
06/12/2008 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
OK RESTROOM WALLS, HARD LIDS