Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: REINFORCED MASONRY PRE-GROUT
Permit Number - T08CM00170
Inspection Description - REINFORCED MASONRY PRE-GROUT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/26/2009 | REINFORCED MASONRY PRE-GROUT | Approved | IVRS - Inspection :* COMPLETED BRICK COLUMNS @ NORTH SIDE OF BLDG. |
|
03/02/2009 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* TAPERED M-Z COLUMN 6' NORTH OF NEC OF RM. #100 TO 16'7" A TO F - SPECIAL INSPECTED OK |
|
02/25/2009 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* CMU EXTERNAL COLUMNS @ NORTH SIDE OF GYM BLDG. FROM 0' TO 4' A TO F AND 3 CMU FROM NE CORNER OF GYM TO THE WEST FROM 4' TO 8' ABOVE TOP OF FOOTING - OK SPECIAL INSPECTED |
|
02/20/2009 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* CMU REINFORCEMENT @ NORTH WALL ROOM #201 TOP OUT AND ALL STAIRWAY WALL TOPOUT |
|
02/18/2009 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* CMU WALLS @ NORTH WALL OF MEZZANINE FROM 24' TO 28'8" WEST AND SOUTH WALLS OF STAIRWELL @ MEZZANINE FROM 20' TO 24'0" & 12" CMU RETAINING WALL @ SEC. FROM 0" TO 2'0" AFFE - SPECIAL INSPECTED |
|
02/12/2009 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) CMU WALL REINFORCEMENT AT SOUTH AND WEST STAIRWAY WALLS FROM 18' TO 20'-NORTH WALL ROOM #201 FROM 20' TO 24' AND EAST STAIRWAY WALL FROM 20" TO 24' AFFE SPECIAL INSPECTED |
|
02/11/2009 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* CMU WALL REINFORCEMENT @ EAST STAIRWELL WALL FROM 16'8" TO 20'8" AFFE AND SOUTHWEST STAIRWELL WALL FROM 14'8" TO 18'8" AFFE -- SPECIAL INSPECTED |
|
02/10/2009 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* CMU WALL REINFORCEMENT AT NORTH WALL OF ROOM #201 FROM 16' TO 20' AFFE - SPECIAL INSPECTION BY WESTERN TECH. |
|
01/29/2009 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* CMU WALL REINFORCEMENT @ EAST WALL RM.#202 FROM 28' TO 32'8" - NWC RM. #100 FROM 12'8" TO 15'4" - EAST WALL RM. #202 FROM 24'8" TO 28'8" AND ROOM #202 32'8" TO 35'4" AFFE -- SPECIAL INSPECTION PERFORMED |
|
01/28/2009 | REINFORCED MASONRY PRE-GROUT | Not ready for Inspection | IVRS - Inspection :* | |
01/27/2009 | REINFORCED MASONRY PRE-GROUT | Denied | IVRS - Inspection : See detailed listing on site.| 999* PLEASE HAVE SPECIAL INSPECTOR ANDREWS & CITY INSPECTOR DABBS CALL ME ABOUT DETAIL T26 MCJ SPLICES AND CONDUITS IN GROUT CELLS |
|
01/26/2009 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* CMU WALL REINFORCEMENT @ EAST WALL OF TREATMENT ROOM #104 -- TOP OUT -- SPECIAL INSPECTION PERFORMED |
|
01/22/2009 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* CMU REINFORCEMENT STEEL @ N/W PIER COLUMN & EAST WALL RM.#104 FROM 8' TO 12' AFFE EAST WALL RM. #100 TOP OUT - NORTH WALL N/W CORNER RM. #104 TO 14 END FROM 14' TO 16' AND WEST WALL OF RM. #104 FROM 16' TO 20'8" AFFE - SPECIAL INSPECTION PERFORMED |
|
01/21/2009 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* CMU WALL REINFORCEMENT @ EAST WALL RM. #100 FROM 24'8" TO 32' AFFE O' NORTH 26'/0' WEST 6' WEST OF SEC. RM. #102 4'8" TO 8'8" AND COLUMN NWC RM. #100 TO 4'8" AFFE |
|
01/20/2009 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* CMU WALL REINFORCEMENT @ EAST WALL ROOM #100 FROM 20'8" TO 24'8" AFFE WEST WALL ROOM #100 FROM 12' TO 16' (INCLUDES BOTH WING WALLS - WEST WALL RM. #104 FROM 17'4" TO 20' AFFE 0' TO 26' NORTH SEC. RM. #102, 0' W - 6' W OF SEC. RM. #102 AND COLUMN @ NWC RM. #100 FROM 0' TO 4'8" AND W.WALL RM. #110 8' TO 10' AFFE -- OK TO GROUT |
|
01/15/2009 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* CMU WALL REINFORCEMENT AT FOLLOWING LOCATIONS: EAST WALL RM. #105 FROM 0' TO 17' NORTH OF GYM WALL FROM 13'4" TO 17'4" AFFE & FROM 17' TO 23' NORTH OF GYM WALL FROM 13'4" TO 15'4" AFFE AND FROM 0' TO 9' SOUTH/0' TO 24' WEST OF HYDRO 107 FROM 13'4" TO 17'4" AFFE SPECIAL INSPECTED |
|
01/13/2009 | REINFORCED MASONRY PRE-GROUT | Partial Approval | CMU WALL REINFORCEMENT AT FOLLOWING LOCATIONS: EAST WALL ROOMS #100 FROM 16'8" TO 20'8" AFFE EAST WALL RM. #110 FROM 12'8" TO 13'8" AFFE (TOP OF WALL) EAST WALL RM. #108 FROM 12'8" TO 16'8" AFFE AND WEST WALL RM. #100 FROM 8'8" TO 12'8" AFFE - SPECIAL INSPECTED |
|
01/12/2009 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* CMU WALL REINFORCEMENT @ LOBBY WEST WALL TO 8'8" ROOM #104 N/E CORNER TOP OUT AND EAST & WEST WALLS @ RM.#108 CONTINUED -- OK SPECIAL INSPECTED |
|
01/12/2009 | REINFORCED MASONRY PRE-GROUT | Partial Approval | CMU WALL REINFORCEMENT AT FOLLOWING LOCATIONS WEST WALL RM. #100 FROM 4'8" TO 8'8" AFFE EAST WALL RMS. #108 & 110 FROM 8'8" TO 12'8" AFFE WEST WALL RM. #110 FROM 0' TO 4'8" AFFE EAST WALL AT ROOMS #105 & 107 FROM 8'8" TO 13'4" (INCLUDES MASONRY LENTEL) AFFE AND NORTH WALL RM.#104 FROM 12'8" TO 17'4" AFEE TOP OUT "SPECIAL INSPECTED" |
|
01/09/2009 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* CMU WALL REINFORCEMENT AT S,W & N WALLS IN ROOMS #100 FROM 0 TO 4:7 - E WALLS RM. #108, 110, WEST WALL RM. #104 FROM 4.7' TO 8.7' AFFE SPECIAL INSPECTED |
|
01/08/2009 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* CMU WALL REINFORCEMENT STEEL @ W.WALL RMS. #105, 106, 107 FROM 0' TO 4'8" - N.WALL @ RMS. #107, 108, 109, 114 & 115 FROM 12'8" TO 14'0" - E.WALL @ RMS. #112 & 115 FROM 12'8" TO 16'8" AND INT. WALLS @ RMS. 111, 112, 113, 114 AND 115 TOP OUT AFFE (SPECIAL INSPECTED) |
|
01/06/2009 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* CMU WALL REINFORCEMENT @ NEC ROOM #100 NEC RM. #104 - EAST WALL ROOM #100; EAST WALL RM. #112 NORTH & SOUTH WALLS RM. #113; EAST & SOUTH WALLS RM. #114 WEST & SOUTH WALLS RM. #108 FROM 8'8" TO 12'8" AFFE AND EAST WALL RM. #105 FROM 8'8" TO 10' AFFE |
|
01/05/2009 | REINFORCED MASONRY PRE-GROUT | Not ready for Inspection | IVRS - Inspection :* RAINED OUT |
|
12/30/2008 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) NORTH AND EAST CMU WALLS AT #106 STAIRS AND NORTH & EAST CMU WALLS AT ROOM #104 FROM 8'-8" TO 12'-8" OK TO GROUT SPECIAL INSPECTED |
|
12/24/2008 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* CMU MASONRY WALL @ GRID EAST WALL ROOM #104 0' TO 5'4" S. OF NEC. S WALL ROOM #104, EAST WALL ROOM #105 0-4.7 AFFE - WEST WALL ROOMS #112 AND 115, NORTH WALL ROOM #115, 114, 109, 108 S & E WALLS ROOM #114 - SE WALLS ROOM #113 EAST WALL ROOM #108 FROM 4'7" TO 8'7" AFFE |
|
12/23/2008 | REINFORCED MASONRY PRE-GROUT | Not ready for Inspection | IVRS - Inspection :* CONTRACTOR CANCELED RAINED OUT |
|
12/18/2008 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* ROOMS #102 THRU #115 FROM 0' TO 4'8" & ROOM #108 EAST AND SOUTH CMU WALL FROM 4'8" TO 8'8" -- OK TO GROUT SPECIAL INSPECTED |
|
12/17/2008 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* CMU WALL REINFORCEMENT @ SOUTH ENTRY INFILL 10' WEST TO 32' WEST @ S/E CORNER OF GYM AND SOUTH WALL OPENING 4'8" TO 8'8" |
|
12/16/2008 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* SOUTH ENTRY INFILL FROM 12' TO 16' OK |
|
12/15/2008 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* CMU WALL REINFORCEMENT @ ROOMS #113 ALL FOUR WALLS; ROOM #109 ALL WALLS EXCEPT NORTH WALL AND ROOMS #114 & 119 ALL EXCEPT NORTH WALL FROM 0' TO 4'8" OK TO GROUT -- SPECIAL INSPECTED |
|
12/12/2008 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* SOUTH ENTRY INFILL OF CMU -- 2ND LIFT FROM 4'0" TO 8'0" OK TO GROUT |
|
12/11/2008 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* SOUTH CMU MASONRY INFILL @ ENTRY CLOSURE |
|
08/22/2008 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* GYM BUILDING CMU TOP OUT COMPLETE - EXCEPT ACCESS OPENING @ S/E CORNER OF SOUTH WALL |
|
08/20/2008 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* NORTH GYM CMU WALL FROM 28'8" TO 32'8" AFFE AND FOUR CONCRETE 24" DUCT OPENINGS @ NORTH GYM CMU WALL |
|
08/15/2008 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* NORTH CMU GYM WALL FROM 24'8" TO 28'8" -- OK |
|
08/13/2008 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* NORTH CMU GYM WALL TO 24'8" WEST HALF |
|
08/12/2008 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1. TOP OUT @ SOUTH CMU WALL 2. 25' @ EAST HALF OR NORTH CMU WALL AND 20'8" @ WEST HALF OF NORTH CMU WALL |
|
08/08/2008 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1. SOUTH CMU EXTERIOR WALL 7TH LIFT FROM 24'8" TO 28'8" 2. NORTH CMU WALL EAST 1/2 TO 16'8" 4TH LIFT |
|
08/06/2008 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) CMU WALL AT NORTH SIDE 4TH LIFT TO 16'-OK TO GROUT |
|
08/05/2008 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* CMU WALLS 1. EAST WALL 6TH LIFT TO 24'8" 2. WEST WALL WINDOW COLUMNS 7TH LIFT TO 28'8" AND NORTH WALL @ N/W CORNER - 4TH LIFT TO 16'8" OK TO GROUT |
|
08/01/2008 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 25' (TOP) WEST WALL AND 24'8" SOUTH WALL |
|
07/30/2008 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* ALL CMU EXTERIOR GYM WALLS TO 20'8" EXCEPT @ TRIPLE DOOR LINTEL ON NORTH WALL @ WEST CORNER - OK TO GROUT |
|
07/28/2008 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* OVER DOORS 101D & E TO 16'8" CMU EXTERIOR GYM WALLS, WEST WALL, FIRST 60 L.F ON EAST WALL FROM SOUTHEAST CORNER NORTH AND FIRST 13 L.F OF SOUTH WALL FROM S/E CORNER FROM 16'8" TO 20'8" AFFE |
|
07/24/2008 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* NORTH CMU GYM WALL FROM N/E CORNER 68' WEST TO 12'8" EAST WALL TO 16'8" & SOUTH WALL ABOVE DOORS #101D AND #101E TO 12'8" -- OK TO GROUT |
|
07/23/2008 | REINFORCED MASONRY PRE-GROUT | Not ready for Inspection | IVRS - Inspection :* RAINED OUT CONTRACTOR CANCELED |
|
07/21/2008 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* CMU GYM WALLS 4TH LIFT FROM 12' TO 16' @ WEST, SOUTH AND EAST WALL TO FIRST CONTROL JOINT OFF SOUTH/EAST CORNER AND 3RD LIFT FROM 8' TO 12' @ BALANCE OF EAST WALL |
|
07/18/2008 | REINFORCED MASONRY PRE-GROUT | Not ready for Inspection | IVRS - Inspection :* CONTRACTOR CANCELED BY PHONE |
|
07/17/2008 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 3RD LIFT @ 12 FOOT - 8 INCH ON WEST & SOUTH WALLS PLUS FIRST 20 L.F FROM S/E CORNER AND 2ND LIFT @ BALANCE OF EAST CMU WALL AND NORTH CMU WALL TO 8'8" AFFE |
|
07/16/2008 | REINFORCED MASONRY PRE-GROUT | Not ready for Inspection | IVRS - Inspection :* CONTRACTOR CANCELED BY PHONE |
|
07/15/2008 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* WEST AND SOUTH CMU WALLS AT GYM BUILDING 2ND LIFT TO 8 FOOT 8 INCH -- OK TO GROUT |
|
07/10/2008 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 4' GYM PERIMETER |