Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T08CM00154
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/24/2008 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
04/15/2008 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1. OK GROUND RODS 2. PLAN CALLS FOR 200 AMP DISCONNECT TO BE INSTALLED TO FEED NEW PANEL 3. EXISTING RIGID PIPING TO DISPENSERS IS NOT DEEP ENOUGH PER NEC 300.5 ALSO, EXISTING PIPING IS EXTREMELY RUSTED ONE EXISTING RACEWAY HAS WIRES THAT CANNOT BE REMOVED BECAUSE PIPE RUSTED CLOSED 4. OK NEW U.G TO CANOPY AREA PIPING TO DISPENSERS NEEDS TO BE CORRECTED |