Permit: T08CM00152

Parcel: 13414001K

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/19/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/13/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. EXISTING 45KVA XFMR DOES NOT HAVE PROPER CONDUCTOR SIZES. DOES NOT HAVE PROPER GROUND
SIZES BONDING SIZES AND GROUNDING ELECTRODE CONDUCTOR SIZE.
2. INSTALL BREAKER BLANK IN 277/480V PANEL
3. INSTALL FILLER PLATE OVER 150MCB IN 120/208V PANEL