Permit: T08CM00142

Parcel: 121060940


Addresses:

1221 N SAHUARA AV

Inspection Status: Not ready for Inspection

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
01/23/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
REINSPECTION FROM YESTERDAY
COURTESY PROVIDED BECAUSE CUSTOMER DID NOT HAVE TIME TO RECAL FOR INSP.

- PIPING TO WH AND STOVE ONLY
- NO FURNACE OR PIPING TO TEST OK
- GAS CLEARANCE GIVEN
- COMPLETE THE REMAINDER OF PREVIOUSLY NOTED CORRECTIONS FOR FINAL APPROVAL
01/17/2008 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- INSTALL LISTED PIPE COUPLINGS NOT THREAD PROTECTORS
- INSTALL FLASHINGS AT ROOF PENETRATIONS
- TEST WITH A 15 PSI GAUGE
- HAVE PRESSURE ON SYSTEM PRIOR TO INSPECTION
- WRAP ALL BELOW GRADE TOOL MARKS
- INSTALL RELOCATED WATER HEATER ON CONCRETE PAD, 4" ABOVE DIRT
- TYPE B VENT REQUIRED, ALSO, CORRECT UNDERSIZED WATER PIPING
- SECURE ENCLOSURE
- INSTALL SEDIMENT TRAP
- HARD PIPE GAS INTO ENCLOSURE
- PIPE T&P DRAIN TO 6" ABOVE GROUND
- BOND TO ELECTRIC GROUND OR WATER PIPE
- SHUT OFF VALVE REQUIRED AT HOUSE
- NO FUTURE TEE CONNECTIONS ALLOWED UNLESS
SHOWN ON PLAN
- SECURE PIPE DROP BEHIND STOVE
- FURNACE SHOWN ON PLAN IS NOT INSTALLED