| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/08/2013 | FRAMING | Approved | IVRS - Inspection :* | |
| 07/12/2013 | FRAMING | Not ready for Inspection | IVRS - Inspection :* | |
| 07/12/2013 | FRAMING | Not ready for Inspection | CANCELED PER GENE | |
| 07/11/2013 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 07/11/2013 | FRAMING | Denied | REVISION NEEDED FOR 13 1/2" TO AN 8" CENTER BEAM | |
| 07/09/2013 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 07/09/2013 | FRAMING | Denied | - PLAN REVISION NEEDED - APPROVED FASTENERS NEEDED IN HANGERS & HOLD DOWNS |
|
| 07/08/2013 | FRAMING | Not ready for Inspection | IVRS - Inspection :* | |
| 07/08/2013 | FRAMING | Not ready for Inspection | CANCELED PER CANDY | |
| 08/27/2008 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) ALL HANGERS BEAMS NOT ON PLAN 2) MISSING NAILS IN HANGERS 3) CAN'T VERIFY SOME HANGER TYPES 4) ANCHORAGE OF LARGE BEAM HANGERS WHAT ARE THEY NAILED INTO 5) LEDGER ANCHOR SPACING NOT PER PLAN 6) NEED TO MEET WITH CONTRACTOR |
|
| 07/18/2008 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED DETAIL FOR BEAM HANGERS, HANGERS AT NORTH END. WHAT WAS USED FOR NAILING ? INTO ? BEAM IS 4" IN FROM CORNER OF HOUSE ? WERE THERE ANY STUDS THAT FAR AWAY FROM CORNER ? 2) MISSED GLU LAM AT CENTER OF PORCH 3) PUT BEAM HANGER SIZES ON PLAN 4) CONTRACTOR PLANS TO PUT TILE ON DECK FLOOR 5) MISSING LAGS AT LEDGER |