Permit: T08CM00141

Parcel: 141282920

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
08/08/2013 FRAMING Approved IVRS - Inspection :*
07/12/2013 FRAMING Not ready for Inspection IVRS - Inspection :*
07/12/2013 FRAMING Not ready for Inspection CANCELED PER GENE
07/11/2013 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
07/11/2013 FRAMING Denied REVISION NEEDED FOR 13 1/2" TO AN 8" CENTER BEAM
07/09/2013 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
07/09/2013 FRAMING Denied - PLAN REVISION NEEDED
- APPROVED FASTENERS NEEDED IN HANGERS & HOLD DOWNS
07/08/2013 FRAMING Not ready for Inspection IVRS - Inspection :*
07/08/2013 FRAMING Not ready for Inspection CANCELED PER CANDY
08/27/2008 FRAMING Not ready for Inspection IVRS - Inspection :*
1) ALL HANGERS BEAMS NOT ON PLAN
2) MISSING NAILS IN HANGERS
3) CAN'T VERIFY SOME HANGER TYPES
4) ANCHORAGE OF LARGE BEAM HANGERS WHAT ARE THEY NAILED INTO
5) LEDGER ANCHOR SPACING NOT PER PLAN
6) NEED TO MEET WITH CONTRACTOR
07/18/2008 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED DETAIL FOR BEAM HANGERS, HANGERS AT NORTH END. WHAT WAS USED FOR NAILING ? INTO ? BEAM IS 4" IN FROM CORNER OF HOUSE ? WERE THERE ANY STUDS THAT FAR AWAY FROM CORNER ?
2) MISSED GLU LAM AT CENTER OF PORCH
3) PUT BEAM HANGER SIZES ON PLAN
4) CONTRACTOR PLANS TO PUT TILE ON DECK FLOOR
5) MISSING LAGS AT LEDGER