Permit: T08CM00138

Parcel: 13734001E

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
04/29/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
04/22/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. RECONNECT FLEX TO LIGHT IN PHONE ROOM
2. HAVE RECEPT ABOVE CEILING COILED UP PHONE ROOM INSTALL TO REQUIRED LOCATION
3. WILL CHECK THIS @ FINAL
03/28/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK ELECTRIC CLOSET
03/27/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS, NEW PANEL DEPTH ADJACENT TO EXISTING PANEL IS INSIDE THE 30" HORIZONTAL WORKING (MINIMUM) REQUIRED BY 110.26 A.3
ALSO, DOORS MUST OPEN AT LEAST 90 DEG. PER 110.26 A.2