Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/29/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 04/22/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. RECONNECT FLEX TO LIGHT IN PHONE ROOM 2. HAVE RECEPT ABOVE CEILING COILED UP PHONE ROOM INSTALL TO REQUIRED LOCATION 3. WILL CHECK THIS @ FINAL |
|
| 03/28/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK ELECTRIC CLOSET |
|
| 03/27/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS, NEW PANEL DEPTH ADJACENT TO EXISTING PANEL IS INSIDE THE 30" HORIZONTAL WORKING (MINIMUM) REQUIRED BY 110.26 A.3 ALSO, DOORS MUST OPEN AT LEAST 90 DEG. PER 110.26 A.2 |