Permit: T08CM00132

Parcel: 10511061R

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T08CM00132

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
06/24/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
06/13/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK CEILING TILES
06/10/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
CEILING INSPECTION - GRID AREA
1. PROVIDE DISCONNECTED MEANS FOR ROLL UP MOTOR
2. EQUIPMENT NOT TO SECURE TO GRID SUPPORT WIRES
3. REMOVE ALL ABANDONED/UNUSED EQUIPMENT
4. NEED LOCKNUTS ON FITTINGS INTO FIXTURES
5. NEED FULL CONDUCTOR UNDER TERMINATIONS
6. SUPPORT WIRES ALL FIXTURES - TRACK 1 EVERY 4 FEET
7. HAVE OVERFILLED WIRENUTS AND J-BOXES
8. WORK NOT COMPLETE/TEMP WIRING TO BE REMOVED

PARTIAL INSPECTION - GO THROUGH MAKE SURE PER PLAN/CODE
06/04/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO ENERGIZE 2 GFI RECEPTACLES NEXT TO PANEL FOR CONSTRUCTION POWER. KEEP ALL PANEL COVERS OK - DO NOT ENERGIZE ANY OPEN WIRING.
06/02/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
05/15/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. ALL TEMPORARY CONSTRUCTION RECEPTACLES TO BE GFI PROTECTED
2. DEMO ALL OLD WIRING AND EQUIPMENT BEHIND WALLS
3. SERVICE NOT TO BE ENERGIZED BEFORE INSPECTION AND APPROVAL, NEED APPROVED PLANS

OK WALL COVER ONLY