Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T08CM00132
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/24/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
06/13/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK CEILING TILES |
|
06/10/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* CEILING INSPECTION - GRID AREA 1. PROVIDE DISCONNECTED MEANS FOR ROLL UP MOTOR 2. EQUIPMENT NOT TO SECURE TO GRID SUPPORT WIRES 3. REMOVE ALL ABANDONED/UNUSED EQUIPMENT 4. NEED LOCKNUTS ON FITTINGS INTO FIXTURES 5. NEED FULL CONDUCTOR UNDER TERMINATIONS 6. SUPPORT WIRES ALL FIXTURES - TRACK 1 EVERY 4 FEET 7. HAVE OVERFILLED WIRENUTS AND J-BOXES 8. WORK NOT COMPLETE/TEMP WIRING TO BE REMOVED PARTIAL INSPECTION - GO THROUGH MAKE SURE PER PLAN/CODE |
|
06/04/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO ENERGIZE 2 GFI RECEPTACLES NEXT TO PANEL FOR CONSTRUCTION POWER. KEEP ALL PANEL COVERS OK - DO NOT ENERGIZE ANY OPEN WIRING. |
|
06/02/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
05/15/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. ALL TEMPORARY CONSTRUCTION RECEPTACLES TO BE GFI PROTECTED 2. DEMO ALL OLD WIRING AND EQUIPMENT BEHIND WALLS 3. SERVICE NOT TO BE ENERGIZED BEFORE INSPECTION AND APPROVAL, NEED APPROVED PLANS OK WALL COVER ONLY |