Inspection History: ELECTRIC - FINAL
Permit Number - T08CM00127
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/18/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
07/31/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. RECALL WHEN EQUIPMENT INSTALLED IN ROOMS 2. RECALL FOR X-RAY ROOM 3. CHECK WITH BUILDING INSPECTOR FOR TEMP C OF O |
|
07/30/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. WATER HEATER DISCONNECT MOUNTED TO HIGH. NEED PROPER SIZE GROUND TO HEATER. NEED PROPER WORKING CLEARANCE ON DISCONNECT 2. EM LIGHT LOBBY NOT WORKING 3. HAVE OPEN CONDUCTORS IN EXHAUST FAN. USE APPROVED WIRING METHOD 4. GROUND AC DISCONNECTS 5. BOND WATER PIPE TO SERVICE |