Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T08CM00125
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/20/2009 | BUILDING - FINAL | Approved | IVRS - Inspection :* 1) POST HOUSE NUMBERS 2) REPLACE DEAD FRONT SCREW WITHOUT POINT |
|
03/24/2009 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) RECEPTACLE AT OUTSIDE AIR HANDLER NEEDS TO BE GFI PROTECTED 2) LOWER CLEANOUT TO GRADE 3) OUTSIDE RECEPTACLE NEED TO BE GFI PROTECTED 4) PLUG ALL HOLES IN SERVICE PANEL 5) NEED BUBBLE COVER ON RECEPT AT SERVICE PANEL 6) ALUMINUM WIRES NEED NO-LUX AT SERVICE PANEL 7) WILL NEED 2 GROUND RODS FOR GROUNDING, BOND GAS AND WATER LINES 8) RECEPTACLE IN UPSTAIRS-BEDROOM REVERSE POLARITY 9) NEED ANTI-TIP AT RANGE |