Inspection History Details
Permit: T08CM00121
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/08/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/06/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 08/05/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SERVICE ENERGIZED PRIOR TO ELECTRICAL INSPECTORS APPROVAL OR CLEARANCE. CT CABINET LOCKED. TRICO LOCK. 2. BOND JUMPERS AHEAD OF OVERCURRENT PROTECTION TOO SMALL. SHOULD BE SIZED PER 250.66 NEC/250.102 C NEC 2/0 C.U AND 1/0 CU 3. HAVE UTILITY UNLOCK CT CAN & RECALL INSPECTION |