Permit: T08CM00121

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/08/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/06/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
08/05/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SERVICE ENERGIZED PRIOR TO ELECTRICAL INSPECTORS APPROVAL OR CLEARANCE. CT CABINET LOCKED. TRICO LOCK.
2. BOND JUMPERS AHEAD OF OVERCURRENT PROTECTION
TOO SMALL. SHOULD BE SIZED PER 250.66 NEC/250.102 C NEC
2/0 C.U AND 1/0 CU
3. HAVE UTILITY UNLOCK CT CAN & RECALL INSPECTION