Permit: T08CM00118

Parcel: 11603197B

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T08CM00118

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/17/2009 MECHANICAL - FINAL Approved IVRS - Inspection :*
06/10/2009 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
TRANSFER DUCTS FROM OTHER AREAS OF BLDG.
WERE NOT INSTALLED INTO KITCHEN
06/08/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. AIR BALANCE REPORT OK EXCEPT FOR KITCHEN EXH. SYSTEM
2. PROVIDE SMOKE CONTAINMENT TEST
3. ALL RTU OVERFUSED
4. RELOCATE OUTSIDE AIR INLET
5. PROVIDE EXTENSION ON EF-1 TO ALLOW PROPER AIR FLOW TO FAN INLET