Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/17/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 06/10/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* TRANSFER DUCTS FROM OTHER AREAS OF BLDG. WERE NOT INSTALLED INTO KITCHEN |
|
| 06/08/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1. AIR BALANCE REPORT OK EXCEPT FOR KITCHEN EXH. SYSTEM 2. PROVIDE SMOKE CONTAINMENT TEST 3. ALL RTU OVERFUSED 4. RELOCATE OUTSIDE AIR INLET 5. PROVIDE EXTENSION ON EF-1 TO ALLOW PROPER AIR FLOW TO FAN INLET |