Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T08CM00118
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/17/2009 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
05/14/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK CEILING EXCEPT ENTRY (MAIN ENTRY) 2) OK TO COVER MULTI PURPOSE, LEAVE TILES OFF WHERE FIXTURES INSTALLED AND J-BOXES, SAME WITH MAIN ENTRY |
|
05/13/2009 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1) SUPPORT M/C PER 300.11 2) BOXES OVER FILLED 3) FINISH MAKE UP FOR ANSUL 4) SECURELY ATTACH FIXTURES TO GRID 410.16 5) FINISH STRAPING CONDUITS ABOVE PANEL "L-1" 6) FINISH INSTALLING EM BALLAST |
|
03/09/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK REMAINDER OF HARD LIDS |
|
03/06/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK 3 SKYLIGHTS AND CANS NORTH END SUPPORT M/C 12" OF CANS |
|
02/10/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. SUPPORT MC CABLES WITHIN 12" OF CANS 2. FIXTURES CANNOT BE DISASSEMBLED OR REASSEMBLED USE APPROVED AND LISTED FOR APPLICATION - SOUTH END OK EAST & WEST SOFFITS CANS OK MAIN ENTRY CANS |