Permit: T08CM00118

Parcel: 11603197B

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T08CM00118

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
06/17/2009 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
05/14/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) OK CEILING EXCEPT ENTRY (MAIN ENTRY)
2) OK TO COVER MULTI PURPOSE, LEAVE TILES OFF WHERE FIXTURES INSTALLED AND J-BOXES, SAME WITH MAIN ENTRY
05/13/2009 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1) SUPPORT M/C PER 300.11
2) BOXES OVER FILLED
3) FINISH MAKE UP FOR ANSUL
4) SECURELY ATTACH FIXTURES TO GRID 410.16
5) FINISH STRAPING CONDUITS ABOVE PANEL "L-1"
6) FINISH INSTALLING EM BALLAST
03/09/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK REMAINDER OF HARD LIDS
03/06/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK 3 SKYLIGHTS AND CANS
NORTH END

SUPPORT M/C 12" OF CANS
02/10/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. SUPPORT MC CABLES WITHIN 12" OF CANS
2. FIXTURES CANNOT BE DISASSEMBLED OR REASSEMBLED USE APPROVED AND LISTED FOR APPLICATION - SOUTH END

OK EAST & WEST SOFFITS CANS
OK MAIN ENTRY CANS