Permit: T08CM00113

Parcel: 12306022G


Addresses:

2200 E ELM ST


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T08CM00113

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/04/2008 MECHANICAL - FINAL Approved IVRS - Inspection :*
05/21/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE INSTALLATION INSTRUCTIONS FOR FAN COILS
2. PROVIDE HOSE CLAMPS ON CONDENSATE HOSE
3. PROVIDE CAP ON LINE SET ROOF PENETRATIONS
4. ALL PVC IS TO BE PRIMED AND GLUED AT ALL JOINTS
5. ALL PVC EXPOSED TO U.V IS TO BE PROTECTED (PAINTED)
6. PVC DRAIN IS TO BE MIN. 1" PIPING DOWN TO FLOOR SINK
7. USE APPROVED METHODS TO TERMINATE COPPER INTO PVC