Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM00113
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/03/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/23/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* COMPLETE ALL ITEMS FROM PREVIOUS INSPECTION HAVE 100% COMPLETE TO AVOID REFEE |
|
| 05/21/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. MARK DISCONNECTS & UNITS WITH UNIT #'s 2. DO NOT FUSE NEUTRAL CONDUCTORS IN DISCONNECTS 3. ENSURE ALL UNITS HAVE PROPER SIZE FUSES 4. INSTALL BUBBLE COVERS ON GFI RECEPT 5. DO NOT USE WHITE WIRE FOR EQUIPMENT GROUNDING CONDUCTOR 6. MARK HVAC PANEL BREAKER IN DISTRIBUTION PANEL 7. MARK WHITE WIRES USED AS PHASE CONDUCTORS IN JUNCTION BOXES AND DISCONNECTS WHEN PART OF CABLE. |