Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/11/2008 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 08/08/2008 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) KITCHEN: GFI CIRCUIT #1 NOT WIRED PER PLAN-UNIT #2 2) HVAC DRAIN LINES NEED TO TERMINATE 6" FROM GROUND 3) OK TO BACKFILL WATER LINE TRENCH 4) ALUMINUM WIRE CONDUCTORS ON BUSS BAR NEED NO LOX 5) NEED CLEANOUT AT BATH GROUPS BOTH UNITS |