Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T08CM00091

Parcel: 135020080

Inspection Status: Approved

Inspection History: ELECTRIC - OUTDOOR LIGHTING

Permit Number - T08CM00091

Inspection Description - ELECTRIC - OUTDOOR LIGHTING

Inspection Status - Approved

Date Description Inspector Results Comments
03/16/2009 ELECTRIC - OUTDOOR LIGHTING Approved IVRS - Inspection :*
02/20/2009 ELECTRIC - OUTDOOR LIGHTING Denied IVRS - Inspection :
There is no plan or job inspection card on site.| 925*
02/19/2009 ELECTRIC - OUTDOOR LIGHTING Not ready for Inspection IVRS - Inspection :*
12/18/2008 ELECTRIC - OUTDOOR LIGHTING Partial Approval IVRS - Inspection :*
12/03/2008 ELECTRIC - OUTDOOR LIGHTING Partial Approval IVRS - Inspection :*
10/23/2008 ELECTRIC - OUTDOOR LIGHTING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. EXPOSE UNDERGROUND RACEWAY/CABLES EVERY 10'
2. PLAN CALLS FOR CIRCUITS TO BE PROTECTED BY 20 AMP BREAKERS
3. WHEN CIRCUIT CONDUCTORS UPSIZED EQUIPMENT GROUNDS TO BE UPSIZED ALSO
4. PLEASE EXPLAIN HOW LIGHT POLE IS GROUNDED
5. PLAN CALLS FOR UNDERGROUND WIRING TO BE UF
6. EXPOSED PVC TO BE SCHEDULE 80
7. POLES TALLER THAN 8' TO HAVE HAND HOLE FOR
SPLICING @ BASE OF POLE. NEC 410.15
8. ONE NEUTRAL PER TERMINAL IN PANEL
9. CANNOT USE GREEN CONDUCTORS FOR PHASE CONDUCTORS
10. STRAP EMT WITHIN 3' OF PANEL. USE PROPER SIZE STRAPS
11. GROUNDS AND NEUTRALS TO BE SEPARATE @ PANEL GROUND BAR TO BE CONNECTED TO PANEL ENCLOSURE
12. INSTALL BREAKERS LISTED FOR USE IN SIEMENS PANEL
13. CALLED SHAFFER ELECTRIC AND THEY STATE THEY ARE NOT CONTRACTOR WHO DID WORK. ELECTRICAL CONTRACTOR RESPONSIBLE FOR WORK TO BE ADDED TO PERMIT. HAVE ELECTRICAL CONTRACTOR ON SITE FOR INSPECTIONS.
14. PROVIDE COPY OF DNR REPORT