Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T08CM00079
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/27/2009 | FRAMING | Approved | IVRS - Inspection :* | |
08/19/2008 | FRAMING | Partial Approval | IVRS - Inspection :* 1) STILL WAITING ON PATIO PORCH TO BE BUILT 2) OK TO SHEETROCK HOUSE 3) VERIFIED APPROVAL ON OVERHEAD SPRINKLERS FROM FIRE MARSHALL |
|
08/18/2008 | FRAMING | Partial Approval | IVRS - Inspection :* 1) NEED INTERMEDIATE APPROVAL FOR FIRE MARSHALL BEFORE I APPROVE INTERMEDIATES |
|
08/13/2008 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GROUND METAL BOX-MASTER BATH CEILING 2) NEED PROTECTION PLATE ON 3/4 WATER SUPPLY TO HOSE BIBB AT LIVING ROOM 3) ADD 2 X STUD AT SERVICE PANEL 4) NO DWV TEST AT KITCHEN AND POWDER ROOM 5) PROTECTION PLATE FLEX GAS LINE AT LAUNDRY ROOM 6) FIRE SEAL MECHANICAL CHASE 2ND FLOOR BEDROOM #3 7) NEED FIRE SPRINKLER OK FROM FIRE MARSHALL |
|
08/12/2008 | FRAMING | Partial Approval | IVRS - Inspection :* 1) OK TO PREPARE CMU WALLS FOR LATH |
|
07/24/2008 | FRAMING | Not ready for Inspection | IVRS - Inspection :* | |
06/12/2008 | FRAMING | Partial Approval | IVRS - Inspection :* | |
06/06/2008 | FRAMING | Partial Approval | IVRS - Inspection :* 1) INSPECTED FIRST LIFT FOR FIREPLACE COURTYARD UP TO DAMPER |