Permit: T08CM00079

Parcel: 116205640

Inspection Status: Approved

Inspection History: REINFORCED MASONRY PRE-GROUT

Permit Number - T08CM00079

Inspection Description - REINFORCED MASONRY PRE-GROUT

Inspection Status - Approved

Date Description Inspector Results Comments
06/04/2008 REINFORCED MASONRY PRE-GROUT Approved IVRS - Inspection :*
06/02/2008 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) OK TO CONTINUE TO NEXT AND LAST LIFT
05/28/2008 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) INSPECTED UP TO 17'-4", OK TO CONTINUE TO NEXT LIFT
05/21/2008 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) OK TO GROUT UP TO 14' AT GARAGE 1ST FLOOR
2) OK TO CONTINUE TO NEXT LIFT IN REMAINDER OF HOUSE
05/14/2008 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) 12"-8" HT. DBL SINGLE BOND BEAMS/BOLTS
05/02/2008 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) INSPECTED FIRST 2 LIFTS-ONLY
2) OK TO CONTINUE TO NEXT LIFT
05/01/2008 REINFORCED MASONRY PRE-GROUT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SOUTH WALL AT COURTYARD WAS DENIED ON 4/22/08 BECAUSE OF MISSING GROUTED BOND BEAM. NO CALL BACK WAS EVER DONE. NEED VERIFICATION THAT BOND BEAM IS GROUTED
04/23/2008 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
INSPECTED FOOTERS FOR STEPS AT COURTYARD
ENTRANCE - OK TO CONTINUE
04/22/2008 REINFORCED MASONRY PRE-GROUT Denied IVRS - Inspection :
See detailed listing on site.| 999*
FOUNDATION DETAIL 108/S3 CALLS FOR GROUTED BOND BEAMS AT 24" O.C