Permit: T08CM00070

Parcel: 133281300


Addresses:

8411 E MEDFORD PL

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
01/15/2008 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
01/09/2008 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. KITCHEN COUNTER RECEPTACLES TO BE GFI PROTECTED
2. INSTALL SMOKE DETECTORS IN BEDROOMS PER MANUFACTURES INSTRUCTIONS
3. SMOKE DETECTOR IN HALLWAY TO BE OPERATIONAL
NEEDS TO BE REPAIRED/REPLACED
4. VERIFY RECEPTACLE IN MASTER BATH IS GFI PROTECTED
5. INSTALL WEATHERPROOF COVER ON OUTDOOR RECEPTACLES. ALSO, NEED WEATHERPROOF BOXES.
6. POOL EQUIPMENT IN DISREPAIR NEEDS TO BE REMOVED OR REPLACED
7. RECALL WHEN READY