Permit: T08CM00023

Parcel: 140120630


Addresses:

5111 S ALEPPO DR


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T08CM00023

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
03/18/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
03/13/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) STAPLE WIRES WITHIN 12" OF J BOXES
2) GROUND ALL METAL BOXES
3) MAKE UP ALL WIRES IN BOXES
4) DO NOT SPLICE 12-2 TO 14-2 WIRES
5) STAPLE/NAIL WIRE MESH 6" ON CENTER TOP & BOTTOM AND AT STUDS