Permit: T08CM00022

Parcel: 12215163A


Addresses:

3150 E GRANT RD


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08CM00022

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/12/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
1. DISCUSSED VARIOUS EQUIP. SAFETY CONCERNS WITH MECH. AND PLUMBING INSPECTORS, NO SAFETY CONCERNS
2. MCC CONTROL CABINET CONTAINS (2) LISTING STAMPS, (1) FOR CABINET AND (1) FOR CONTROL RELAYS & WIRING BY "ARIZONA CONTROL INC." ALSO (2) OPERATION SEQUENCE PANELS INSIDE, BOTH CONTAINED DUAL LISTINGS
3. DRAWINGS HAD A BOLD PRINT NOTE TO INFORM THAT THERE IS SUPPLEMENTAL DRAWINGS FOR EQUIP & PLACEMENT. THESE WERE ON SITE AS WELL AS SHOP DRAWINGS AND DIAGRAMS FOR MCC ALL EQUIP. WAS SHOWN ON DIAGRAM AND APPROVED THRU STANTEC
4. OTHER ITEMS OF CONCERN FROM LAST INSPECTION HAVE BEEN CORRECTED
08/11/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. DISCONNECTING MEANS FOR COMPRESSORS NEEDED
2. FINISH POLE LIGHT
3. PER MANUFACTURES STATEMENT WE NEED A THIRD PARTY NRTL EVALUATION OF CARWASH EQUIPMENT
08/04/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE 314.20 BATHROOM & LIGHTS
2. PVC CONDUIT ABOVE GRADE TO BE SCHED 80 - CITY AMENDMENTS
3. INSTALL RECEPTACLE COVER IN DRINKING FOUNTAIN
4. BONDING AS PER 250.97
5. PROTECT CONDUCTORS AT PVC CONDUIT 350.46
6. TIGHTEN GROUND TERMINAL IN
TIME CLOCK/CONTACTOR BOX
7. FINISH CIRCUIT DIRECTORIES - 408.4
8. GROUND PLUG MOLD
9. VERIFY ALL COMPONENTS COVERED UNDER LISTING MARK