Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM00022
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/12/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1. DISCUSSED VARIOUS EQUIP. SAFETY CONCERNS WITH MECH. AND PLUMBING INSPECTORS, NO SAFETY CONCERNS 2. MCC CONTROL CABINET CONTAINS (2) LISTING STAMPS, (1) FOR CABINET AND (1) FOR CONTROL RELAYS & WIRING BY "ARIZONA CONTROL INC." ALSO (2) OPERATION SEQUENCE PANELS INSIDE, BOTH CONTAINED DUAL LISTINGS 3. DRAWINGS HAD A BOLD PRINT NOTE TO INFORM THAT THERE IS SUPPLEMENTAL DRAWINGS FOR EQUIP & PLACEMENT. THESE WERE ON SITE AS WELL AS SHOP DRAWINGS AND DIAGRAMS FOR MCC ALL EQUIP. WAS SHOWN ON DIAGRAM AND APPROVED THRU STANTEC 4. OTHER ITEMS OF CONCERN FROM LAST INSPECTION HAVE BEEN CORRECTED |
|
08/11/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. DISCONNECTING MEANS FOR COMPRESSORS NEEDED 2. FINISH POLE LIGHT 3. PER MANUFACTURES STATEMENT WE NEED A THIRD PARTY NRTL EVALUATION OF CARWASH EQUIPMENT |
|
08/04/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE 314.20 BATHROOM & LIGHTS 2. PVC CONDUIT ABOVE GRADE TO BE SCHED 80 - CITY AMENDMENTS 3. INSTALL RECEPTACLE COVER IN DRINKING FOUNTAIN 4. BONDING AS PER 250.97 5. PROTECT CONDUCTORS AT PVC CONDUIT 350.46 6. TIGHTEN GROUND TERMINAL IN TIME CLOCK/CONTACTOR BOX 7. FINISH CIRCUIT DIRECTORIES - 408.4 8. GROUND PLUG MOLD 9. VERIFY ALL COMPONENTS COVERED UNDER LISTING MARK |