Permit: T08CM00022

Parcel: 12215163A


Addresses:

3150 E GRANT RD


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T08CM00022

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
08/12/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
08/04/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
07/29/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) NEED A NEUTRAL TO SMALL SERVICE DISCONNECT
07/23/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. CONDUIT TO BLOCK WALL NOT INSPECTED
2. BONDING AS PER 250.97 IS NEEDED
3. FILL UNUSED OPENINGS IN BOXES AND GUTTERS
4. IF GUTTER IS MORE THAN 30 CIRCUITS DERATE - 366.6
5. BOND RISER
6. USE CORRECT SIZED LUGS FOR CONDUCTORS
7. ONLY ONE CONDUCTOR PER LUG LISTING
8. BOND JUMPER TO BE SIZED PER 250.102 & 250.66
9. PLANS NOT REFLECTIVE OF SERVICE INSTALLED
10. POST BOND AND HAVE ELECTRICAL DONE 8' & BELOW