Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T08CM00022
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/12/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
08/04/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
07/29/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) NEED A NEUTRAL TO SMALL SERVICE DISCONNECT |
|
07/23/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CONDUIT TO BLOCK WALL NOT INSPECTED 2. BONDING AS PER 250.97 IS NEEDED 3. FILL UNUSED OPENINGS IN BOXES AND GUTTERS 4. IF GUTTER IS MORE THAN 30 CIRCUITS DERATE - 366.6 5. BOND RISER 6. USE CORRECT SIZED LUGS FOR CONDUCTORS 7. ONLY ONE CONDUCTOR PER LUG LISTING 8. BOND JUMPER TO BE SIZED PER 250.102 & 250.66 9. PLANS NOT REFLECTIVE OF SERVICE INSTALLED 10. POST BOND AND HAVE ELECTRICAL DONE 8' & BELOW |