Permit: T08CM00021

Parcel: 13001004B

Inspection Status: Approved

Inspection History: ELECTRIC - TEMPORARY SERVICE

Permit Number - T08CM00021

Inspection Description - ELECTRIC - TEMPORARY SERVICE

Inspection Status - Approved

Date Description Inspector Results Comments
10/30/2008 ELECTRIC - TEMPORARY SERVICE Approved
05/08/2008 ELECTRIC - TEMPORARY SERVICE Partial Approval IVRS - Inspection :*
1) FUSE 400 AMP SERVICE DISCONNECT DOWN TD 1/3 FOR TEMP PEDESTAL LESS THAN 25" DISTANCE
2) WILL NEED TO REVISE PLAN FOR EXISTING SERVICE INSTALL PRIOR TO FINAL
05/07/2008 ELECTRIC - TEMPORARY SERVICE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. BOND SERVICE DISCONNECT AND CONNECTORS AHEAD OF OVER CURRENT PROTECTION PER 250 NEC
2. 400 AMP FUSES FOR TEMP POWER STAND?
3. OPEN CT & TERM. CAN TO INSPECT TERMINATIONS
05/05/2008 ELECTRIC - TEMPORARY SERVICE Not ready for Inspection IVRS - Inspection :*
NO ONE ON SITE
NO TEMP SERVICE ON SITE