Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMPORARY SERVICE
Permit Number - T08CM00021
Inspection Description - ELECTRIC - TEMPORARY SERVICE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/30/2008 | ELECTRIC - TEMPORARY SERVICE | Approved | ||
| 05/08/2008 | ELECTRIC - TEMPORARY SERVICE | Partial Approval | IVRS - Inspection :* 1) FUSE 400 AMP SERVICE DISCONNECT DOWN TD 1/3 FOR TEMP PEDESTAL LESS THAN 25" DISTANCE 2) WILL NEED TO REVISE PLAN FOR EXISTING SERVICE INSTALL PRIOR TO FINAL |
|
| 05/07/2008 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. BOND SERVICE DISCONNECT AND CONNECTORS AHEAD OF OVER CURRENT PROTECTION PER 250 NEC 2. 400 AMP FUSES FOR TEMP POWER STAND? 3. OPEN CT & TERM. CAN TO INSPECT TERMINATIONS |
|
| 05/05/2008 | ELECTRIC - TEMPORARY SERVICE | Not ready for Inspection | IVRS - Inspection :* NO ONE ON SITE NO TEMP SERVICE ON SITE |