Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T08CM00016
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/07/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
04/25/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) CIRCUITS WITH #12 AND #14 WIRES INTERCONNECTED NEED TO BE ON 15 AMP BREAKERS 2) USE ROMEX CONNECTORS ON WIRES IN METAL JUNCTION BOXES 3) JUNCTION BOXES MUST REMAIN ACCESSIBLE AFTER SHEETROCK |