Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UFER
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/19/2008 | ELECTRIC - UFER | Approved | IVRS - Inspection :* | |
| 02/14/2008 | ELECTRIC - UFER | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) YOU USED A SPLIT BOLT 2) THE PROPER CLAMP IS LIKE THE ONE YOU USED ON THE PIPE AND THE GROUND ROD 3) THE COPPER WIRE CANNOT COME IN DIRECT CONTACT WITH THE REBAR |
|
| 02/12/2008 | ELECTRIC - UFER | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) UFER GROUND WIRE MUST BE ATTACHED TO REBAR WITH A UFER CLAMP ONLY 2) CORRECT AND HAVE REINSPECTED BEFORE CONCRETE |