Permit: T08CM00014

Parcel: 116021740


Addresses:

2860 W HIGHCLIFF DR

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
02/06/2008 FRAMING Approved IVRS - Inspection :*
02/04/2008 FRAMING Partial Approval IVRS - Inspection :*
1) NEED TO PROTECT ALL WIRE CONDUCTORS GOING THRU DRILLED HOLES IN 2 X WITH A MEATAL PROTECTION PLATE MIN. 1.25 (1 1/4")
2) NEED TO STAPLE ALL WIRES THAT ARE LOOSE AND HANGING IN CEILING AND ABOVE CAN LIGHTS