Permit: T08CM00012

Parcel: 115041660


Addresses:

716 E MABEL ST


Inspection Status: Not ready for Inspection

Inspection History: BUILDING - FINAL

Permit Number - T08CM00012

Inspection Description - BUILDING - FINAL

Inspection Status - Not ready for Inspection

Date Description Inspector Results Comments
01/06/2009 BUILDING - FINAL Not ready for Inspection VISITED SITE TO SPECIFICALLY LOOK AT STAIRS.

STAIRS MAY COMPLY WITH INTENT OF R311.5 & R311.5.8. BY ALTERING "SPIRAL" PORTION OF STEPS SO THAT RUN IS CONSISTENT OVER THE 3 STEP SPAN.

A) EACH STEP TO BE ROTATED FROM A SINGLE VERTICAL LINE EQUAL TO CORNER AT THE INSIDE OF THE STEP.
B) EACH STEP TO HAVE AN EQUAL RUN OF 7.5" OR GREATER WHEN MEASURED AT A POINT 12" FROM THE ROTATIONAL POINT.
C) OWNER WILL BE REQUIRED TO ADD AN ADDITIONAL HANDRAIL ALONG "OUTSIDE" CORNER OF STAIR RUN (ENTIRE RUN FROM 1ST TO 2ND FLOOR)
12/31/2008 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
1) CANCELLED PER R.D.
12/23/2008 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) STAIRS NOT PER CODE-WILL NEED TO GET AN APPEAL FROM BLDG OFFICIAL OR BUILD TO CODE
2) MISSING ARC-FAULT BREAKER IN BEDROOM
12/19/2008 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
1) CANCELLED PER CONTRACTOR
12/18/2008 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO ACCESS 10:30 AM, CALLED NUMBER-NO ANSWER
2) LEFT MESSAGE ON MACHINE TO RECALL INSPECTION